B. Pirollet - TS CV - Aout 2006 Ventilation experience LHCB Concept général. Présentation d’aout 2006 Point sur travaux. Extraction; gaz/ fumées Planning
B. Pirollet - TS CV - Aout 2006
areas - technical caverns. Cold smoke extraction principle Point 8 UX85 protected area UX85 experimental area UAEX 892 UAEX 893 UAPE831 UAPE832 Wall UAIS UAIT
B. Pirollet - TS CV - Aout 2006 PointAreaModePulsionExtractionGaz 1UX 15Normal2x x 5000 Smoke extraction (*)2x x 5000 USA 15Normal1x x Smoke extraction1x x UX 25Normal1x x 6000 Smoke extraction (*)2x x UXC 55Normal1x x 5000 Smoke extraction (*)2x x 5000 USC 55Normal1x x 5000 Smoke extraction2x x UX 85Normal1x x x 2500 Smoke extraction (*)1x x x 2500 UX 85 PANormal1x x x 2500 Smoke extraction (*)1x x x 2500 *Extraction gaz = smoke extraction
B. Pirollet - TS CV - Aout 2006
Cold smoke extraction Detection All the air handling units of the concerned area are automatically stopped (TS/CV) Smoke extraction mode activated by fire men (fire men cubicle) Fire men Air handling units in normal mode restarted by TS-CV End of fire men action During extraction mode extraction filters will be by-passed No action with RP Material design 400°C/2h
B. Pirollet - TS CV - Aout 2006 Planning Unité de pulsion 831 caverne UX En service Unité de pulsion 832 zone protégée Semaine 30 Extraction caverne UX (bouchon ouvert)En service Extraction caverne UX (bouchon fermé)Semaine 29 Extraction zone protégée Semaine 26 Essais mise au point Semaines 30 a 35 Réception Semaine 35